Fix chiller chilling when it is off #10793

Draft
wants to merge 4 commits into
base: develop
Choose a base branch
from
Draft

Conversation

mjwitte
Copy link
Contributor

@mjwitte mjwitte commented Oct 17, 2024

Pull request overview

  • Throw warning for chiller condition where the chiller has been shut off due to zero condenser water flow, but produces phantom cooling if the evaporator flow is > zero (probably because it's on a series-active branch). e.g. from local annual simulation for
   ** Warning ** Chiller should be off, evap flow rate=1.4389689535199999, but EvapInletTemp=7.38915769242907 is != EvapOutletTemp=6.900575452477234, EvapInletNodeNum.Temp =7.38915769242907, EvapOutletNodeNum).Temp=6.900575452477234
   **   ~~~   ** MyLoad=-833.961772284167, RunFlag=true, QEvaporator=0, QCondenser=0, EvapMassFlowRate=1.4389689535199999, CondMassFlowRate = 0, Power=0 
   **   ~~~   **  Environment=RUN PERIOD 1, at Simulation time=05/16 09:15 - 09:30
   ** Warning ** Chiller should be off, evap flow rate=1.4389689535199999, but EvapInletTemp=7.396212077191015 is != EvapOutletTemp=6.6766091195480035, EvapInletNodeNum.Temp =7.396212077191015, EvapOutletNodeNum).Temp=6.6766091195480035
   **   ~~~   ** MyLoad=-868.746569242984, RunFlag=true, QEvaporator=0, QCondenser=0, EvapMassFlowRate=1.4389689535199999, CondMassFlowRate = 0, Power=0 
   **   ~~~   **  Environment=RUN PERIOD 1, at Simulation time=05/16 09:23 - 09:30
   ** Warning ** Chiller should be off, evap flow rate=1.4389689535199999, but EvapInletTemp=7.440021886600333 is != EvapOutletTemp=6.1678902101263375, EvapInletNodeNum.Temp =7.440021886600333, EvapOutletNodeNum).Temp=6.1678902101263375
   **   ~~~   ** MyLoad=-1084.7813548033087, RunFlag=true, QEvaporator=0, QCondenser=0, EvapMassFlowRate=1.4389689535199999, CondMassFlowRate = 0, Power=0 
   **   ~~~   **  Environment=RUN PERIOD 1, at Simulation time=05/20 09:00 - 09:15
  • Next commit fixes the issue by setting MyLoad to zero if lack of condenser water flow causes the chiller to be off. No more of the above warnings are produced (with a full annual regression).

Pull Request Author

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Title of PR should be user-synopsis style (clearly understandable in a standalone changelog context)
  • Label the PR with at least one of: Defect, Refactoring, NewFeature, Performance, and/or DoNoPublish
  • Pull requests that impact EnergyPlus code must also include unit tests to cover enhancement or defect repair
  • Author should provide a "walkthrough" of relevant code changes using a GitHub code review comment process
  • If any diffs are expected, author must demonstrate they are justified using plots and descriptions
  • If changes fix a defect, the fix should be demonstrated in plots and descriptions
  • If any defect files are updated to a more recent version, upload new versions here or on DevSupport
  • If IDD requires transition, transition source, rules, ExpandObjects, and IDFs must be updated, and add IDDChange label
  • If structural output changes, add to output rules file and add OutputChange label
  • If adding/removing any LaTeX docs or figures, update that document's CMakeLists file dependencies

Reviewer

This will not be exhaustively relevant to every PR.

  • Perform a Code Review on GitHub
  • If branch is behind develop, merge develop and build locally to check for side effects of the merge
  • If defect, verify by running develop branch and reproducing defect, then running PR and reproducing fix
  • If feature, test running new feature, try creative ways to break it
  • CI status: all green or justified
  • Check that performance is not impacted (CI Linux results include performance check)
  • Run Unit Test(s) locally
  • Check any new function arguments for performance impacts
  • Verify IDF naming conventions and styles, memos and notes and defaults
  • If new idf included, locally check the err file and other outputs

@mjwitte mjwitte added the Defect Includes code to repair a defect in EnergyPlus label Oct 17, 2024
@mjwitte
Copy link
Contributor Author

mjwitte commented Oct 17, 2024

@rraustad @EnergyArchmage This condition occurs when the chiller has a load, but the chiller shuts down here due to zero condenser water flow and leaves calculate with

// Set initial mass flow rates
if (this->CondenserType == DataPlant::CondenserType::WaterCooled) {
this->CondMassFlowRate = this->CondMassFlowRateMax;
PlantUtilities::SetComponentFlowRate(state, this->CondMassFlowRate, this->CondInletNodeNum, this->CondOutletNodeNum, this->CDPlantLoc);
PlantUtilities::PullCompInterconnectTrigger(
state, this->CWPlantLoc, this->CondMassFlowIndex, this->CDPlantLoc, DataPlant::CriteriaType::MassFlowRate, this->CondMassFlowRate);
if (this->CondMassFlowRate < DataBranchAirLoopPlant::MassFlowTolerance) {
if (this->EvapMassFlowRate < DataBranchAirLoopPlant::MassFlowTolerance) {
// Use PlantUtilities::SetComponentFlowRate to decide actual flow
PlantUtilities::SetComponentFlowRate(
state, this->EvapMassFlowRate, this->EvapInletNodeNum, this->EvapOutletNodeNum, this->CWPlantLoc);
}
return;
}
}

This has been set before this exit:

this->EvapOutletTemp = state.dataLoopNodes->Node(this->EvapOutletNodeNum).Temp;

(which seems wrong, wouldn't you want to intialize outlet=inlet before that actual calcs happen?)

After this, update thinks the chiller is on, because there is a load and the evap mass flow rate is >0 so it skips the chiller of block:

if (MyLoad >= 0 || !RunFlag) { // Chiller not running so pass inlet states to outlet states
// Set node conditions
state.dataLoopNodes->Node(this->EvapOutletNodeNum).Temp = state.dataLoopNodes->Node(this->EvapInletNodeNum).Temp;
state.dataLoopNodes->Node(this->CondOutletNodeNum).Temp = state.dataLoopNodes->Node(this->CondInletNodeNum).Temp;
if (this->CondenserType != DataPlant::CondenserType::WaterCooled) {
state.dataLoopNodes->Node(this->CondOutletNodeNum).HumRat = state.dataLoopNodes->Node(this->CondInletNodeNum).HumRat;
state.dataLoopNodes->Node(this->CondOutletNodeNum).Enthalpy = state.dataLoopNodes->Node(this->CondInletNodeNum).Enthalpy;
state.dataLoopNodes->Node(this->CondInletNodeNum).MassFlowRate = 0.0;
state.dataLoopNodes->Node(this->CondOutletNodeNum).MassFlowRate = 0.0;
}

And those line setting condense mass flow rates to zero seem wrong, because the chiller could have flow forced through the condenser even when it's off. this is ok, it's for aircooled condenser.

@mjwitte
Copy link
Contributor Author

mjwitte commented Oct 17, 2024

Oh, never mind the condenser flow rate comment, those lines are for aircooled condenser.

Copy link

⚠️ Regressions detected on macos-14 for commit ce1be3e

Regression Summary
  • ERR: 1

@rraustad
Copy link
Contributor

Line 1939 does seem wrong as something to do before a potential return at line 1970. Also, as an observation, if the return at 1970 happens I would think the calc routine would want to inform other later functions that the chiller RunFlag = false,

@mjwitte
Copy link
Contributor Author

mjwitte commented Oct 17, 2024

Line 1939 does seem wrong as something to do before a potential return at line 1970. Also, as an observation, if the return at 1970 happens I would think the calc routine would want to inform other later functions that the chiller RunFlag = false,

Given the arguments here

void ElectricEIRChillerSpecs::simulate(
    EnergyPlusData &state, const PlantLocation &calledFromLocation, bool FirstHVACIteration, Real64 &CurLoad, bool RunFlag)

ElectricEIRChillerSpecs::calculate(EnergyPlusData &state, Real64 &MyLoad, bool const RunFlag)

Perhaps MyLoad should be set to zero before returning?

@rraustad
Copy link
Contributor

Perhaps MyLoad should be set to zero before returning?

Probably, because that return value for &CurLoad will be used by the calling routine (I think) to update the remaining load.

@rraustad
Copy link
Contributor

If the calling routine does use &CurLoad then I would think that MyLoad should represent exactly what load the chiller met. I don't think I have ever considered that before.

@EnergyArchmage
Copy link
Contributor

Yes, that is the idea. So it can update remaining load for dispatch to other machines if any.

Copy link

⚠️ Regressions detected on macos-14 for commit 41d5e18

Regression Summary
  • EIO: 1
  • ERR: 1
  • ESO Big Diffs: 1
  • Table Big Diffs: 1

Copy link

⚠️ Regressions detected on macos-14 for commit c9e51bd

Regression Summary
  • EIO: 1
  • ERR: 1
  • ESO Big Diffs: 1
  • Table Big Diffs: 1

@@ -1962,6 +1962,8 @@ void ElectricEIRChillerSpecs::calculate(EnergyPlusData &state, Real64 &MyLoad, b
state, this->CWPlantLoc, this->CondMassFlowIndex, this->CDPlantLoc, DataPlant::CriteriaType::MassFlowRate, this->CondMassFlowRate);

if (this->CondMassFlowRate < DataBranchAirLoopPlant::MassFlowTolerance) {
// Shut chiller off if there is no condenser water flow
MyLoad = 0.0;
Copy link
Contributor

@rraustad rraustad Oct 19, 2024

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This does look like it boils down to this. I looked at PullCompInterconnectTrigger to see what that was trying to accomplish. This code looks like it can be deleted. I'm not asking for that to happen here but it's extra clock cycles. Removed in #10794,

    // Check to make sure we didn't reuse the index in multiple components
    if (CurCriteria.CallingCompLoopNum != plantLoc.loopNum || CurCriteria.CallingCompLoopSideNum != plantLoc.loopSideNum ||
        CurCriteria.CallingCompBranchNum != plantLoc.branchNum || CurCriteria.CallingCompCompNum != plantLoc.compNum) {
        // Diagnostic fatal: component does not properly utilize unique indexing
    }